Input Line Reactors 230Vac & 460Vac DC Drives

3% Average Impedance

Mentor MP & Quantum MP 230Vac

Drive
Amps

Inductance

 (µH)

Watts Loss Chassis Mount NEMA 1 Enclosed
Order Code

Dimensions

H X W X D (in)

Weight (lbs) Order Code

Dimensions

H X W X D (in)

Weight (lbs)
y25 21 530 38.3 LRL0021A-C 5.3X4.4X3.3 4.2 LRL0021A-E 13.3X13.2X13.1 22.2
y45 46 300 77 LRL0046A-C 6X7.2X3.8 13 LRL0046A-E 13.3X13.2X13.1 31
y75 83 170 119 LRL0083A-C 6X7.2X4.3 19 LRL0083A-E 13.3X13.2X13.1 37
y105 104 120 94 LRL0104A-C 6X7.2X6.5 22 LRL0104A-E 13.3X13.2X13.1 40
y155 160 80 110 LRL0160A-C 7.5X9.3X6.8 34 LRL0160A-E 13.3X13.2X13.1 52
y210 200 60 159 LRL0200A-C 7.5X9.3X7.0 34 LRL0200A-E 24X16.9X18.4 61
z350 322 50 300 LRL0322A-C 7.5X9.3X9 57 LRL0322A-E 24X16.9X18.4 84
z420 414 33 333 LRL0414A-C 8.8X9X9.5 78 LRL0414A-E 47X26.5X24.9 222
z550 515 25 314 LRL0515A-C 8.8X9X9.5 81 LRL0515A-E 47X26.5X24.9 225
z700 600 20 375 LRL0600A-C 8.8X9X10.5 86 LRL0600A-E 47X26.5X24.9 230
z825 750 17 468 LRL0750A-C 8.8X9X11.5 105 LRL0750A-E 47X26.5X24.9 249
z900 850 15 798 LRL0850-C 15.5X17.8X14.5 195 LRL0850-E 47X27X25 339
z1200 1200 9 980 LRL1200-C 15.5X17.8X14.5 195 LRL1200-E 72X26.5X25 415
z1850 Consult Microcon or Factory

y = Mentor MP or Quantum MP.

z = Mentor MP

Consult Microcon for different impedance requirements and NEMA 3R outdoor enclosure options.


Mentor MP & Quantum MP 460 Vac

Drive
Amps

Inductance

 (µH)

Watts Loss Chassis Mount NEMA 1 Enclosed
Order Code

Dimensions

H X W X D (in)

Weight (lbs) Order Code

Dimensions

H X W X D (in)

Weight (lbs)
y25 28 820 36 LRM0028A-C 6.1X6X3.3 9 LRM0028A-E 13.3X13.2X13.1 28.4
y45 46 550 99 LRM0046A-C 6X7.2X4.3 17 LRM0046A-E 13.3X13.2X13.1 35
y75 83 290 155 LRM0083A-C 7X9X6.5 26 LRM0083A-E 13.3X13.2X13.1 44
y105 104 230 200 LRM0104A-C 7X9X7 28 LRM0104A-E 13.3X13.2X13.1 46
y155 160 155 195 LRM0160A-C 7.5X9.3X8.3 49 LRM0160A-E 13.3X13.2X13.1 67
y210 200 115 224 LRM0200A-C 7.5X9.3X7.0 49 LRM0200A-E 24X16.9X18.4 82
y350 322 70 383 LRM0322A-C 8.8X10.8.3X8.5 76 LRM0322A-E 47X26.5X24.9 220
y420 414 66 531 LRM0414A-C 8.8X9X11.5 98 LRM0414A-E 47X26.5X24.9 242
y550 515 50 496 LRM0515A-C 8.8X9X12 118 LRM0515A-E 47X26.5X24.9 262
y700 600 40 747 LRM0600A-C 11.5X14.4X12.5 144 LRM0600A-E 47X26.5X24.9 288
y825 750 35 630 LRM0750A-C 11.5X14.4X12.5 179 LRM0750A-E 47X26.5X24.9 323
y900 850 27 930 LRM0850-C 15.5X17.8X15.5 215 LRM0850-E 47X27X25 359
z1200 1200 19 1130 LRM1200-C 15.5X17.8X17.8 275 LRM1200-E 72X26.5X25 495
z1850 Consult Microcon or Factory

y = Mentor MP or Quantum MP.

z = Mentor MP

Consult Microcon for different impedance requirements and NEMA 3R outdoor enclosure options.


Mentor MP 575 Vac

Drive
Amps

Inductance

 (µH)

Watts Loss Chassis Mount NEMA 1 Enclosed
Order Code

Dimensions

H X W X D (in)

Weight (lbs) Order Code

Dimensions

H X W X D (in)

Weight (lbs)
MP25A5 28 1300 93.8 LRH0028A-C 6.1X6X3.3   LRH0028A-E 13.3X13.2X13.1 28.4
MP45A5 46 550 99 LRM0046A-C 6X7.2X4.3   LRM0046A-E 13.3X13.2X13.1 35
MP75A5 83 290 105 LRM0083A-C 7X9X6.5   LRM0065A-E 13.3X13.2X13.1 40
MP105A5 104 230 200 LRM0104A-C 7X9X7   LRM0104A-E 13.3X13.2X13.1 46
MP155A5 160 155 195 LRM0160A-C 7.5X9.3X8.3   LRM0160A-E 13.3X13.2X13.1 67
MP210A5 200 115 224 LRM0200A-C 7.5X9.3X7.0   LRM0200A-E 24X16.9X18.4 82
MP350A5 322 70 383 LRM0322A-C 8.8X10.8.3X8.5   LRM0322A-E 47X26.5X24.9 220
MP470A5 414 66 531 LRM0414A-C 8.8X9X11.5   LRM0414A-E 47X26.5X24.9 242
MP700A5 750 35 838 LRM0750A-C 11.5X14.4X12.5   LRM0750A-E 47X26.5X24.9 323
MP825A5 750 35 838 LRM0850-C 15.5X17.8X15.5   LRM0750-E 47X27X25 323
MP1200A5 1200 30 1550 LRH1200-C 15.5X17.8X17.8   LRH1200-E 72X26.5X25 610
MP1850A5 Consult Microcon or Factory

Mentor MP 690 Vac

Drive
Amps

Inductance

 (µH)

Watts Loss Chassis Mount NEMA 1 Enclosed
Order Code

Dimensions

H X W X D (in)

Weight (lbs) Order Code

Dimensions

H X W X D (in)

Weight (lbs)
MP350A6 322 70 383 LRM0322A-C 8.8X10.8X8.5 76 LRM0322A-C 8.8X10.8X8.5 76
MP470A6 414 66 531 LRM0414A-C 8.8X9X11.5 98 LRM0414A-C 8.8X9X11.5 98
MP700A6 750 35 838 LRM0750A-C 11.5X14.4X12.5 179 LRM0750A-C 11.5X14.4X12.5 179
MP825A6 750 35 838 LRM750A-C 11.5X14.4X12.5 179 LRM0750A-C 11.5X14.4X12.5 179
MP1200A6 1200 30 1550 LRH1200-C 15.4X17.4X18.3 390 LRH1200-E 72X26.5X25 610
MP1850A6 Consult Microcon or Factory

Consult factory for different % impedance requirements and NEMA 3R outdoor enclosure options.


Home / Contact Us / Products / Service / Sales /Supported Product / Powertec Support / Serviced Products / Feedback


 

Microcon Technologies Inc.

1105 Crestlawn Drive, Unit # D8 & D9

Mississauga, Ontario L4W 1A7 Canada

Tel: (905) 602-4770

Fax: (905) 602-4779

e-mail: [email protected]